I’m trying to figure out an issue with my ice machine in my restaurant. It’s an indigo I 1400n series. And once I clear the fault code and let it start making ice it only gets into the freeze cycle about 4 minutes before the head pressure is at 450psi and the HPCO cuts power. It always returns to 300psi on the head and stays pretty well at 45psi suction. Both seem within the proper area since the condenser is roof mounted and sitting in 100 degree heat.
It’s been hot today but not as hot as the last week, and this is the first time we’ve seen this code since installing the unit. Any advice of other things to check before I call an A/C guy out to scavenge some Freon out and drop my pressures?